Chapter 1 Basics and Assembly Manual VIPA System SLIO
1-14 HB300E - PS-CM - Rev. 11/28
Wiring
Terminals with spring clamp technology are used for wiring. The spring
clamp technology allows quick and easy connection of your signal and
supply lines.
In contrast to screw terminal connections this type of connection is vibration
proof.
10mm
U
max
: 240V AC / 30V DC
I
max
: 10A
Cross section: 0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length: 10mm
Wiring procedure
Insert a suited screwdriver at an angel into the square opening as
shown.
Press and hold the screwdriver in the opposite direction to open the
contact spring.
Insert the stripped end of wire into the round opening. You can use
wires with a cross section of 0.08mm2 to 1.5mm2.
By removing the screwdriver, the wire is securely fixed via the spring
contact to the terminal.