Manual VIPA System 300V Chapter 4 CANopen
HB130E - IM - Rev. 08/26 4-57
Index Sub-
Index
Name Type Attr. Map. Default value Meaning
0x6237 0x00 32bit digital
input block
Unsigned8 ro N depending on
the compo-
nents fitted
Number of available digital
32bit output blocks
0x01 1st output
block
Unsigned32 rw N 1st error value digital output
block
... ... ... ... ... ... ...
0x12 18th output
block
Unsigned32 rw N 18th error value digital output
block
Presupposed that the error mode is active, device failures set the output to
the value configured by this object.
Index Sub-
Index
Name Type Attr. Map. Default value Meaning
0x6401 0x00 2byte input
block
Unsigned8 ro N depending on
the compo-
nents fitted
Number of available analog
inputs
0x01 1st input
channel
Unsigned16 ro Y 1st analog input channel
... ... ... ... ... ... ...
0x24 24th input
channel
Unsigned16 ro Y 24th analog input channel
Index Sub-
Index
Name Type Attr. Map. Default value Meaning
0x6411 0x00 2byte output
block
Unsigned8 ro N depending on
the compo-
nents fitted
Number of available
analog outputs
0x01 1st output
channel
Unsigned16 ro Y 1st analog output
channel
... ... ... ... ... ... ...
0x24 24th output
channel
Unsigned16 ro Y 24th analog output
channel
Fault state digital
output 32 bit
Analog input
Analog output