Manual VIPA System 300V Chapter 1 Basics
HB130E - IM - Rev. 08/26 1-5
Wiring by means of spring pressure connections (CageClamps) at the
front connector
Core cross-section 0.08...2.5mm
2
or 1.5 mm
2
Total isolation of the wiring at module change
Potential separation of all modules to the backplane bus
Burst/ESD acc. IEC 61000-4-2/IEC 61000-4-4 (up to level 3)
Shock resistance acc. IEC 60068-2-6 / IEC 60068-2-27 (1G/12G)
Operating temperature: 0 ... +60°C
Storage temperature: -25 ... +70°C
Relative humidity: 5...95% without condensation
Ventilation by means of a fan is not required
For project engineering of your DP slave you may transfer your projects
from your PC to the CPU serial via MPI by using the "Green Cable". Please
also regard the hints to the Green Cable in this chapter!
Every Profibus slave has an internal power supply. This power supply
requires DC 24V. In addition to the electronics on the bus coupler, the
supply voltage is also used to power any modules connected to the
backplane bus. Please note that the maximum current that the integrated
power supply can deliver to the backplane bus is 3.5A.
The power supply is protected against reverse polarity and overcurrent.
The digital in-/output modules of the System 300V from VIPA are pin and
function compatible to Siemens.
The project engineering happens in the SIMATIC manager from Siemens.
Note!
For programming of a System 300V CPU from VIPA please use always the
CPU 315-2DP (6ES7 315-2AF03 V1.2) from Siemens in the hardware
catalog.
Please note the Profibus address 1 of the CPU 31x is system dependent
reserved.
For the project engineering, a thorough knowledge of the Siemens
SIMATIC manager and the hardware configurator is required!
Reliability
Environmental
conditions
Green Cable
for project
engineering
Integrated
power supply
Compatibility

Other manuals for VIPA System 300V