Chapter 4 CANopen Manual VIPA System 300V
4-66 HB130E - IM - Rev. 08/26
Technical data
Electrical data VIPA 353-1CA00
Power supply DC 24V (20.4 ... 28.8) via front from ext. power supply
Current consumption max. 0.7A
Output current backplane bus max. 3.5A
Isolation
AC 500V
Status indicator by means of LEDs located on the front
Connectors/interfaces 9pin D-type (socket) CAN-Bus connection
CAN-Bus interface
Connection 9pin D-type plug
Network topology Linear bus, active bus termination at one end, tap lines
permitted.
Medium Screened three-core cable, unscreened cable permitted -
depending on environment.
Data transfer rate 10kBaud to 1MBaud
Max. overall length 1000m at 50kBaud without repeaters
Digital inputs/outputs Any combination of max. of 32 I/O modules per coupler.
Combination with peripheral
modules
max. no. of modules 32 (depending on current consumption)
max. inputs/outputs 80Byte each (80Byte = 10 PDOs à 8Byte)