Chapter 4 CANopen Manual VIPA System 300V
4-66 HB130E - IM - Rev. 08/26
Technical data
Electrical data VIPA 353-1CA00
Power supply DC 24V (20.4 ... 28.8) via front from ext. power supply
Current consumption max. 0.7A
Output current backplane bus max. 3.5A
Isolation
≥ AC 500V
Status indicator by means of LEDs located on the front
Connectors/interfaces 9pin D-type (socket) CAN-Bus connection
CAN-Bus interface
Connection 9pin D-type plug
Network topology Linear bus, active bus termination at one end, tap lines
permitted.
Medium Screened three-core cable, unscreened cable permitted -
depending on environment.
Data transfer rate 10kBaud to 1MBaud
Max. overall length 1000m at 50kBaud without repeaters
Digital inputs/outputs Any combination of max. of 32 I/O modules per coupler.
Combination with peripheral
modules
max. no. of modules 32 (depending on current consumption)
max. inputs/outputs 80Byte each (80Byte = 10 PDOs à 8Byte)
Dimensions and weight
Dimensions (WxHxD) in mm 25.4x76x78
Weight 80g
CANopen slave
IM 353CAN