Manual VIPA System 300V Chapter 3 Profibus DP
HB130E - IM - Rev. 08/26 3-25
IM 353-1DP01 - DP-V1 slave - Project engineering
For project engineering a DP master engineering tool can be used like the
Siemens SIMATIC manager. Here you assign the according Profibus DP
slave modules to the DP master.
A direct assignment takes place via the Profibus address that you set at
the DP slave address selector.
By installing the corresponding GSD file the IM 353-1DP01 is listed at the
hardware catalog as "VIPA_353-1DP01 (DP-V0 or DP-V1)".
You'll find this at:
Profibus DP > Additional Field devices> I/O > VIPA_System_300V
VIPA supplies a data medium with every Profibus module. This medium
contains among others all the GSD files of the VIPA Profibus modules.
Depending on the installed GSD file the following modules are listed at the
hardware catalog.:
Module GSD file
VIPA 353-1DP01 (DP-V0) VI0009AF.gsd
VIPA 353-1DP01 (DP-V1) VI0109AF.gsd
Install the appropriate GSD file in your engineering tool. For more
information see manual of you engineering tool.
• Mount your Profibus system.
• Start your project engineering tool with a new project.
• Configure a master system and create a new Profibus subnet.
• For the project engineering of the IM 353-1DP01 take the "VIPA 353-
1DP01 (DPV0)" or "VIPA 353-1DP01 (DPV1)" for each functionality from
the hardware catalog and drag it to the DP master subnet.
• Enter a Profibus address between 1 and 99 into the properties of the DP
slave and set the same address at the address lever.
• Parameterize the DP slave (see parameters).
• Transfer your project to the PLC.
General
DP-V0/DP-V1
functionality by
GSD file
Project
engineering