Chapter 3 Profibus DP Manual VIPA System 300V
3-26 HB130E - IM - Rev. 08/26
Note
Please note to place the following modules during hardware configuration
to the first three slots:
Config for Slot1
Config for Slot2
Config for Slot3
These modules are automatically placed using the Siemens SIMATIC
Manager:
At usage of the IM 353-1DP01 (DP-V0) you have the following parameter
data:
Byte Bit 7 ... Bit 0 Default
0 Bit 2 ... 0: 0 (fix)
Bit 3: 0 = WD-Timebase 10ms
1 = WD-Timebase 1ms
Bit 4: 0 (fix)
Bit 5: 0 = Publisher-Mode not available
1 = Publisher-Mode available
00h
1)
1 00h (fix) 00h
2 08h (fix) 08h
3 0Ah (fix) 0Ah
4 81h (fix) 81h
5 00h (fix) 00h
6 00h (fix) 00h
7 Bit 0: 0 = Identifier-related diagnostic enable
1 = Identifier-related diagnostic disable
Bit 1: 0 = Module status enable
1 = Module status disable
Bit 2: 0 = Channel-related diagnostic enable
1 = Channel-related diagnostic disable
Bit 3: 0 (fix)
bit 4: 0 (fix)
Bit 5: 0 = V0: Diagnostic interrupt not available
1 = V0: Diagnostic interrupt available
Bit 6: 0 = V0: Hardware interrupt not available
1 = V0: Hardware interrupt available
Bit 7: 0 (fix)
70h
8 Bit 7 ... 0: 0 (fix) 00h
9 ... 12 00h (fix) 00h
1)
Using the Siemens SIMATIC Manager this value is automatically set and can not be
changed.
Parameter data
IM 353-1DP01
DP-V0