SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type
Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern"
ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
Where practicable smoke alarms should be placed on the
ceiling.
It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
300mm of a corner of a ceiling and a wall
300mm of a light fitting
400mm of an air-conditioning vent
400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Conn
ect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Conne
ct
A
E-Loop
N
I
-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c.
Interconnection
Neutral
II210720-AZ