FOR USERS
ashing.
Note: Compulsory defrosting intervals should be more than 30 minutes and the compressor
should run for more than 10 minutes at heating mode.
8. Temperature display conversion between °C and °F:
Press " " and " " together for 5 seconds to switch between °C and °F.
9. Wi-Fi setting
Please kindly check the last page.
2.3. Advanced application
2.3.1. Parameter Checking
a. Press and together for 5 seconds to enter “Parameter Checking” status, the
parameter codeP0” and the parameter value0” will display on the screen, such as “P0
0”, which means water pump running way is continuous.
b. In “Parameter Checking” status, press or to check the parameters.
2.3.2. Parameter Modication
InParameter Checkingstatus, press to enter the “Parameter Modicationmode,
press or to change the values, then press to conrm and quitParameter
Modication” mode, press to quit “Parameter Checking” status.
2.3.3. Parameter list
NO. Content Adjust range
Step
length
P0 Water Pump Running Way
0: Continuous
1: Water temp control
2: Time/water temp
control
1
P1
Time Setting
(Only available when the water pump running way is set to
“2”)
10 ~ 120 min 5 min
P2
Compressor Continuously Running Time between
Defrosting Mode
30 ~ 90 min 1 min
P3 Defrosting Entry Temp -17~0°C / 1~32°F C /1°F
P4 Maximum Defrosting Running Time 1 ~ 12 min 1 min
P5 Defrosting Exit Temp 8~3C /46~8F 1°C /1°F