Table 13 Thermal Disinfection Parameters
Parameter
Name
Range
Default
Description
G01
Setpoint
60~70°C
70°C
Hot water thermal disinfection target
temperature
G02
Time of Duration
0~60min
0min
Duration of thermal disinfection cycle
(0 is off)
G03
Start Time
0~23h
0h
Time when thermal disinfection is on
G04
Work cycle
1~30days
7days
Thermal disinfection cycle schedule
(default is once every 7 days)
Table 14 Temperature Parameters
Parameter
Name
Range
Default
Description
R01
Hot Water
Setpoint
R06~R07
55°C
Hot water target setpoint
R02
Heating Setpoint
R08~R09
40°C
Heating target setpoint
R03
Cooling Setpoint
R08~R09
12°C
Cooling target setpoint
R04
Power-on Return
Difference
0.5~10°C
2°C
Hysteresis differential for heating and
cooling setpoint
R05
Standby Temp
Difference
*
2°C
Temperature difference above the hot
water setpoint to return to standby mode
R06
Min Hot Water
Setpoint
*
40°C
Minimum hot water setpoint allowed
R07
Max Hot Water
Setpoint
*
65°C
Maximum hot water setpoint allowed
R08
Min Heating
Setpoint
*
20°C
Minimum heating setpoint allowed
R09
Max Heating
Setpoint
*
50°C
Maximum heating setpoint allowed
R10
Min Cooling
Setpoint
*
12°C
Minimum cooling setpoint allowed
R11
Max Cooling
Setpoint
*
20°C
Maximum cooling setpoint allowed
R12
Electric Heating
0/1/2
00
Electric Heating Function, 0 for not used,
1 for in-line heater, 2 for tank immersion
R13
Electric Heater
Start Difference
*
C
Hysteresis differential for electric heater
R14
Electric Heater
Start AT
*
C
Outside temperature below which the
electric heater is enabled
R15
Delay of Electric
Heater
*
30mins
Delay time for electric heater to start as
outside temperature falls below R14
R16
Electric Heater
Start at Once AT
*
-C
Outside temperature below which the
electric heater starts without delay