3.6 Wiring Watlow Series 97
Input 1 Wiring
Figure 3.6a – Thermocouple
Available on all units
Impedance: 20M
Figure 3.6b – RTD (2- or 3-Wire) 100 Platinum
Available on all units
Input 2 Wiring
Figure 3.6c – Digital Event
97 _ 1 - _ _ _ _ - _ _ _ _
Voltage input
3-36VÎ (dc) Event Input High State
0-2VÎ (dc) Event Input Low State
Contact closure
0-2k Event Input Low State
> 23k Event Input High State
2.67k
EVENT +
3
EVENT
-
1
20k
100
+5V
1
2
3
4
5
6
7
1
5
6
7
S1
S2
S3
3-wire
1
2
3
4
5
6
7
6
7
S1
S3
5
2-wire
jumper 5 to 6
10
8
1
2
3
4
5
6
7
13 14 15
11
12
16 17 18
19 20 21
9
- 6
+7
NOTE:
Successful installation
requires five steps:
Choose the controller’s
hardware configuration
and model number
(Appendix);
Choose a sensor
(Chapters 3 and 6, and
Appendix);
Install the controller
(Chapter 2);
• Wire the controller
(Chapter 3) and
• Configure the controller
(Chapters 4, 5 and 6).
ç
WARNING:
To avoid damage to
property and equipment,
and/or injury of loss of
life, use National Electric
Code (NEC) standard
wiring practices to
install and operate the
Series 97. Failure to do
so could result in such
damage, and/or injury or
death.
ç
CAUTION:
Maintain isolation
between input 1 and
input 2 to prevent a
ground loop. A ground
loop may cause incorrect
readings, dashes across
the upper display or the
display of error codes.
Failure to follow this
guideline could result in
damage to equipment
and product.