Single-phase Alarm
Non-latching Alarm Option
DC _ _ - _ _ _ _ - [H, S] _ _ _
NOTE:If you plan to wire
multiple DIN-A-MITE
alarm outputs, you need
to include an
intermediate relay for
each DIN-A-MITE used.
The Watlow DIN-A-MITE alarm option provides
a common alarm output for open-heater or
shorted SCR conditions. This is a non-latching
alarm.
• A shorted SCR alarm is detected when there is
no command signal and a load current is
detected. The alarm output is then energized.
• An open-heater or partial open-heater state is
detected when a command signal is present and
a reduced or no output current is detected. The
alarm output is then energized.
Setup Procedure for Open-Heater Alarm
(For Input Control Signal type S option only)
1. With the temperature control wired to the
DIN-A-MITE SCR power control, set the
temperature control output to “full on” (20mA
for 4 to 20mA output, or 5V for 0 to 5V output).
2. Adjust the open heater alarm adjustment
potentiometer until the alarm indicator light on
the front panel is full on, with no intermittent
cycling.
3. Slowly adjust the potentiometer until the
open heater indicator light just turns full off,
with no intermittent cycling.
If you are getting false alarms, the adjustment is
probably set too sensitive and should be re-
adjusted towards the off condition of the open-
heater indicator light. The open heater pot is
adjusted counter clockwise to increase
sensitivity to open heater detect (red light on
sooner) or clockwise to desensitize to open
heater detect (red light on later).
No setup procedure required for shorted SCR alarm.
Load Current -
Single phase load
wire passes through
one CT. Number of
passes through CT:
5 to 9A 2
10 to 65A 1