Watlow EZ-ZONE
®
PM Integrated Controller 98 Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`CAL]
[FCty]
Calibration Menu
[`Mu]
[ Mv]
Calibration Menu
(1 to 2)
Electrical Mea-
surement
Read the raw
electrical value for
this input in the
units correspond-
ing to the Sensor
Type (Setup Page,
Analog Input
Menu) setting.
-3.4e38 to 3.4e38 Always Instance 1
Map 1 Map 2
400 400
Instance 2
Map 1 Map 2
480 490
0x68 (104)
1 to 2
0x15 (21)
- - - - float
R
[ELi;o]
[ELi.o]
Calibration Menu
(1 to 2)
Electrical Input
Offset
Change this value
to calibrate the
low end of the in-
put range.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
378 378
Instance 2
Map 1 Map 2
458 468
0x68 (104)
1 to 2
0xA (10)
- - - - float
RWES
[ELi;S]
[ELi.S]
Calibration Menu
(1 to 2)
Electrical Input
Slope
Adjust this value
to calibrate the
slope of the input
value.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
380 380
Instance 2
Map 1 Map 2
460 470
0x68 (104)
1 to 2
0xB (11)
- - - - float
RWES
[ELo;o]
[ELo.o]
Calibration Menu
(1 or 3)
Electrical Output
Offset
Change this value
to calibrate the
low end of the out-
put range.
Menu 2 calibrates
output 3.
-1,999.000 to 9,999.000 0.0 the control-
ler has
process
outputs: 1
or 3
Instance 1
Map 1 Map 2
728 848
Instance 3
Map 1 Map 2
808 928
0x76 (118)
1 or 3
5
- - - - float
RWES
[ELo;S]
[ELo.S]
Calibration Menu
(1 or 3)
Electrical Output
Slope
Adjust this value
to calibrate the
slope of the output
value.
Menu 2 calibrates
output 3.
-1,999.000 to 9,999.000 1.0 the control-
ler has
process
outputs: 1
or 3
Instance 1
Map 1 Map 2
730 850
Instance 3
Map 1 Map 2
810 930
0x76 (118)
1 or 3
6
- - - - float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E:
EEPROM
S:
User
Set

Table of Contents