PM Integrated Controller • 80 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[R;typ]
[R.tyP]
Global Menu
Ramping Type
[rate] Rate (81)
[``ti] Time (143)
Time If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
- - - - 4414
0x7A (122)
1
26 (38)
- - - - uint
RWE
[P;typ]
[P.tyP]
Global Menu
Profile Type
Set the profile start-
up to be based on a
set point or a process
value.
[StPt] Set Point (85)
[`Pro] Process (75)
Set Point If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
2534 4354
0x7A (122)
1
8
- - - - uint
RWE
[`GSE]
[ gSE]
Global Menu
Guaranteed Soak
Enable
Enables the guaran-
teed soak deviation
function in profiles.
[`oFF] Off (62)
[``on]
On (63)
Off If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
2530 4350
0x7A (122)
1
6
- - - - uint
RWE
[GSd1]
[gSd1]
Global Menu
Guaranteed Soak
Deviation 1
Set the value of the
deviation band that
will be used in all
profile step types.
The process value
must enter the devia-
tion band before the
step can proceed.
0.0to9,999.000°Forunits
0.0to5,555.000°C
10.0°For
units
6.0°C
If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
2532 4352
0x7A (122)
1
7
- - - - float
RWE
[GSd2]
[gSd2]
Global Menu
Guaranteed Soak
Deviation 2
Set the value of the
deviation band that
will be used in all
profile step types.
The process value
must enter the devia-
tion band before the
step can proceed.
0.0to9,999.000°Forunits
0.0to5,555.000°C
10.0°For
units
6.0°C
If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
- - - - 4420
0x7A (122)
1
0x29 (41)
- - - - float
RWE
[`Si;a]
[ Si.a]
Global Menu
Source Instance A
Set the source for
WE1.
5 to 12 1 If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
- - - - 4390
0x7A (122)
1
0x1A (26)
- - - - uint
RWES
[`Si;B]
[ Si.b]
Global Menu
Source Instance B
Set the source for
WE2.
5 to 12 1 If 4th digit
in controller
part num-
ber is an R,
B, N or E.
Instance 1
Map 1 Map 2
- - - - 4392
7A (122)
1
0x1B (27)
- - - - uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User