Watlow EZ-ZONE
®
PM Integrated Controller • 81 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[poti]
[Poti]
Global Menu
Power Out Time
If profile is running
and power is lost,
profile will resume
where it left off pro-
vided time set has
not expired prior to
power restoration.
0 to 9999 seconds 0 If 4th digit
in controller
part num-
ber is a B or
an E.
Instance 1
Map 1 Map 2
- - - - 4484
7A (122)
1
0x49 (73)
- - - - uint
RWE
[C;led]
[C.LEd]
Global Menu
Communications
LED Action
Turns comms LED
on or off for selected
comms ports.
[Con1] Comm port 2 (1189)
[Con2] Comm port 1 (1190)
[both] Comm port 1 and 2
(13)
[`off] Off (62)
both Always Instance 1
Map 1 Map 2
1856 2326
0x6A (103)
1
0x0E (14)
- - - - uint
RWES
[2one]
[Zone]
Global Menu
Zone
Turns Zone LED on
or off based on selec-
tion.
[`off] Off (62)
[``on] On (63)
On Always Instance 1
Map 1 Map 2
- - - - 2350
0x6A (103)
1
0x1A (26)
- - - - uint
RWES
[Chan]
[Chan]
Global Menu
Channel
Turns Channel LED
on or off based on
selection.
[`off] Off (62)
[``on] On (63)
On Always Instance 1
Map 1 Map 2
- - - - 2352
0x6A (103)
1
0x1B (27)
- - - - uint
RWES
[d;prs]
[dPrS]
Global Menu
Display Pairs
Defines the number
of Display Pairs.
1 to 10 2 Always Instance 1
Map 1 Map 2
- - - - 2354
0x6A (103)
1
0x1C (28)
- - - - uint
RWES
[`d;ti]
[ d.ti]
Global Menu
Display Time
Time delay in tog-
gling between chan-
nel 1 and channel 2.
0 to 60 0 Always Instance 1
Map 1 Map 2
- - - - 2356
0x6A (103)
1
0x1D (29)
- - - - uint
RWES
[USr;S]
[USr.S]
Global Menu
User Settings Save
Save all of this con-
troller's settings to
the selected set.
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
[none] None (61)
None Always
Instance 1
Map 1 Map 2
26 26
0x(101)
1
0xE (14)
118 uint
RWE
[USr;r]
[USr.r]
Global Menu
User Restore Set-
tings
Replace all of this
controller's settings
with another set.
[FCty] Factory (31)
[none] None (61)
[SEt1] User Set 1 (101)
[SEt2] User Set 2 (102)
None
Instance 1
Map 1 Map 2
24 24
0x65
(101)
1
0xD (13)
117 uint
RWE
[CoM]
[`SEt]
Communications Menu
PCoL]
[PCoL]
Communications 1
Protocol
Set the protocol of
this controller to the
protocol that this
network is using.
[`Std] Standard Bus (1286)
[Mod] Modbus RTU (1057)
Modbus Always if
digit 8 is a
"1".
Instance 1
Map 1 Map 2
2492 2972
0x96 (150)
1
7
- - - - uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set