PM Integrated Controller 82 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
`Ad;S]
[ Ad.S]
Communications 1
Address Standard
Bus
Set the network ad-
dress of this control-
ler. Each device on
the network must
have a unique ad-
dress.
The Zone Display on
the front panel will
display this number.
1 to 16 1 Protocol
is set to
Standard-
bus.
Instance 1
Map 1 Map 2
2480 2960
0x96 (150)
1
1
- - - - uint
RWE
[Ad;M]
[Ad.M]
Communications (1
or 2)
Address Modbus
Set the network ad-
dress of this control-
ler. Each device on
the network must
have a unique ad-
dress.
1 to 247 1 Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2482 2962
0x96 (150)
1
2
- - - - uint
RWE
[bAUd]
[bAUd]
Communications (1
or 2)
Baud Rate Modbus
Set the speed of this
controller's communi-
cations to match the
speed of the serial
network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600 Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2484 2964
0x96 (150)
1
3
- - - - uint
RWE
[`PAr]
[ PAr]
Communications
Parity Modbus (1
or 2)
Set the parity of this
controller to match
the parity of the se-
rial network.
[none] None (61)
[EuEn] Even (191)
[`odd] Odd (192)
None Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2486 2966
0x96 (150)
1
4
- - - - uint
RWE
[`C_f]
[ C_F]
Communications (1)
Temperature Units
Select whether this
communications
channel will display
in Celsius or Fahr-
enheit.
[```f] Fahrenheit (30)
[```C] Celsius (15)
F Always Instance 1
Map 1 Map 2
2490 2970
0x96 (150)
1
6
- - - - uint
RWE
[M;hL]
[M.hL]
Communications (1
or 2)
Modbus Word Or-
der
Select the word or-
der of the two 16-bit
words in the floating-
point values.
[Lohi] Low-High (1331)
[hiLo] High-Low (1330)
Low-High Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2488 2968
0x96 (150)
1
5
- - - - uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set