PM Integrated Controller • 90 • Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter name
Description
Range Default Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Data
Type
&
Read/
Write
[~SEC]
[ SEC]
Step Type Parameters
Seconds
Select the seconds (plus
Hours and Minutes) for a
timed step.
0 to 59
0 Step Type is
set to Time or
Soak.
Instance 1
Map 1 Map 2
2578 4508
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
5
uint
RWE
[W;Pi]
[W.Pi]
Step Type Parameters
Wait For Process In-
stance
Select which analog input
Wait For Process will use.
1 or 2
1 Step Type is
set to Wait For
Process and
the controller
has two pro-
cess inputs.
Instance 1
Map 1 Map 2
2598 4528
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xF (15)
uint
RWE
W;P1]
[W.P1]
Step Type Parameters
Wait For Process Value
Select which analog input
Wait For Process will use.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
0.0°For
units
-18.0°C
Step Type is
set to Wait For
Process.
Instance 1
Map 1 Map 2
2590 4520
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xB (11)
float
RWE
W;P2]
[W.P1]
Step Type Parameters
Wait For Process Value
Select which analog input
Wait For Process will use.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
0.0°For
units
-18.0°C
Step Type is
set to Wait For
Process.
Instance 1
Map 1 Map 2
- - - - 4560
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0x1F (31)
float
RWE
WE;1]
[WE.1]
Step Type Parameters
Wait Event (5-12)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2586 4516
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
9
uint
RWE
[WE;2]
[WE.2]
Step Type Parameters
Wait Event (5-12)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2588 4518
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xA (10)
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User Set