EasyManua.ls Logo

Watlow ez-zone pm - Page 97

Watlow ez-zone pm
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PM Integrated Controller 94 Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`iid]
[ iid]
Custom Setup (1
to 20)
Instance ID
Select which
instance of the
parameter will be
selected.
1 to 4 If there
is only
one valid
instance
for corre-
sponding
class mem-
ber then
not active,
otherwise
active.
- - - - - - - - - - - - - - - -
[`LoC]
[FCty]
Security Setting Menu
[LoC;o]
[LoC.o]
Security Setting
Operations Page
Change the secu-
rity level of the
Operations Page.
1 to 3 2 Always
- - - - - - - - - - - - - - - -
[LoC;P]
[LoC.P]
Security Setting
Profiling Page
Change the secu-
rity level of the
Profiling Page.
1 to 3 3 Always
- - - - - - - - - - - - - - - -
[pas;e]
[LoC.P]
Security Setting
Password Enable
Turn security fea-
tures on or off.
[`off] Off
[``on] On
Off Always
- - - - - - - - - - - - - - - -
[rLoC]
[rLoC]
Security Setting
Read Lock
Set the read se-
curity clearance
level. The user can
access the selected
level and all lower
levels.
If the Set Lockout
Security level is
higher than the
Read Lockout Se-
curity, the Read
Loc
kout Security
level takes prior-
ity.
1 to 5 5 Always
- - - - - - - - - - - - - - - -
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E:
EEPROM
S:
User
Set