Watlow EZ-ZONE
®
PMI Controller • 97 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
s.Lo
S.Lo
Analog Input (1 to 2)
Scale Low
Set the low scale for
process inputs. This
value, in millivolts,
volts or milliamps,
will correspond to
the Range Low out-
put of this function
block.
-100.00 to 1,000.00 0.0 Instance 1
Map 1 Map 2
388 388
Instance 2
Map 1 Map 2
468 478
0x68
(104)
1 to 2
0xF (15)
6 4015 float
RWES
s.hi
S.hi
Analog Input (1 to 2)
Scale High
Set the high scale
for process inputs.
This value, in mil-
livolts, volts or milli-
amperes, will corre-
spond to the Range
High output of this
function block.
-100.00 to 1,000.00 20.0 Instance 1
Map 1 Map 2
390 390
Instance 2
Map 1 Map 2
470 480
0x68
(104)
1 to 2
0x10
(16)
7 4016 float
RWES
r.Lo
r.Lo
Analog Input (1 to 2)
Range Low
Set the low range
for this function
block's output.
-1,999.000 to
9,999.000
0.0 Instance 1
Map 1 Map 2
392 392
Instance 2
Map 1 Map 2
472 482
0x68
(104)
1 to 2
0x11
(17)
8 4017 float
RWES
r.hi
r.hi
Analog Input (1 to 2)
Range High
Set the high range
for this function
block's output.
-1,999.000 to
9,999.000
9,999 Instance 1
Map 1 Map 2
394 394
Instance 2
Map 1 Map 2
474 484
0x68
(104)
1 to 2
0x12
(18)
9 4018 float
RWES
p.EE
P.EE
Analog Input (1 to 2)
Process Error En-
able
Turn the Process Er-
ror Low feature on
or off.
off Off (62)
LoФІ Low (53)
Off
Instance 1
Map 1 Map 2
418 418
Instance 2
Map 1 Map 2
498 508
0x68
(104)
1 to 2
0x1E
(30)
10 4030 uint
RWES
p.EL
P.EL
Analog Input (1 to 2)
Process Error Low
Value
If the process value
drops below this
value, it will trigger
an input error.
-100.00 to 1,000.00 0.0 Instance 1
Map 1 Map 2
420 420
Instance 2
Map 1 Map 2
500 510
0x68
(104)
1 to 2
0x1F
(31)
11 4031 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set