Watlow EZ-ZONE
®
PMI Controller • 99 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
i.Ca
i.CA
Analog Input (1 to 2)
Calibration Offset *
Offset the input
reading to compen-
sate for lead wire
resistance or other
factors that cause
the input reading to
vary from the actual
process value.
-1,999.000 to
9,999.000°F or units
-1,110.555 to
5,555.000°C
0.0 Instance 1
Map 1 Map 2
382 382
Instance 2
Map 1 Map 2
462 472
0x68
(104)
1 to 2
0xC (12)
2 4012 float
RWES
ain
Ain
Analog Input (1 to 2)
Analog Input Value
*
View the process
value.
Note:
Ensure that the Er-
ror Status (below)
indicates no error
(61) when reading
this value using a
field bus protocol.
If an error exists,
the last known value
prior to the error
occurring will be re-
turned.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
360 360
Instance 2
Map 1 Map 2
440 450
0x68
(104)
1 to 2
1
0 4001 float
R
i.Er
i.Er
Analog Input (1 to 2)
Input Error *
View the cause of
the most recent er-
ror.
nonE None (61)
OpEn Open (65)
shrt Shorted (127)
E.ЛЏ Measurement Er-
ror (140)
E.CaL Bad Calibration
Data (139)
Er.ab Ambient Error
(9)
E.rtd RTD Error (141)
faiL Fail (32)
- - - -
Instance 1
Map 1 Map 2
362 442
Instance 2
Map 1 Map 2
362 452
0x68
(104)
1 to 2
2
1 4002 uint
R
d.bi
sEt
Digital Bus Menu (J1939 CAN)
d.bi
d.bi
Digital Bus (1 to 6)
J1939 Instance
Select the desired
instance.
1 to 6 - - - - - - - - - - - - - - - - - - - - float
RW
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set