Watlow EZ-ZONE
®
PMI Controller • 138 • Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
FiL
FiL
Math (1)
Filter
Filtering smooths
out the output sig-
nal of this function
block. Increase the
time to increase fil-
tering.
0.0 to 60.0 seconds 0.0 Instance 1
Map 1 Map 2
- - - - 3054
0x7D
(125)
1
0x1C
(28)
- - - - 25028 float
RWES
sof
sEt
Special Output Function Menu
Fn
Fn
Special Output (1)
Function
Set the function to
match the device it
will operate.
oFF Off (62)
uA.C Motorized Valve
(1508)
Co.C Compressor
Control (1506)
Off Instance 1
Map 1 Map 2
- - - - 3856
0x87
(135)
1
9
181 35009 uint
RWES
SFn.A
SFn.A
Special Output (1)
Source Function A
Set the type of
function that will
be used for this
source.
nonE None (61)
PФІr Power (73)
h.Pr Heat Power
(160)
C.Pr Cool Power
(161)
None Instance 1
Map 1 Map 2
- - - - 3840
0x87
(135)
1
1
182 35001 uint
RWES
Si.A
Si.A
Special Output (1)
Source Instance A
Set the instance of
the function select-
ed above.
1 to 2 1 Instance 1
Map 1 Map 2
- - - - 3844
0x87
(135)
1
3
183 35003 uint
RWES
SFn.b
SFn.b
Special Output (1)
Source Function B
Set the type of
function that will
be used for this
source.
nonE None (61)
PФІr Power (73)
h.Pr Heat Power
(160)
C.Pr Cool Power
(161)
None Instance 1
Map 1 Map 2
- - - - 3842
0x87
(135)
1
2
184 35002 uint
RWES
Si.b
Si.b
Special Output (1)
Source Instance B
Set the instance of
the function select-
ed above.
1 to 2 1 Instance 1
Map 1 Map 2
- - - - 3846
0x87
(135)
1
4
185 35004 uint
RWES
Pon.A
Pon.A
Special Output (1)
Input A Turn On
Compressor 1 power
on level.
-100.00 to 100.00% 0 Instance 1
Map 1 Map 2
- - - - 3874
0x87
(135)
1
0x12
(18)
186 35018 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set