PMI Controller 139 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
PoF.A
PoF.A
Special Output (1)
Input A Turn Off
Compressor 1 power
off level.
-100.00 to 100.00% 5 Instance 1
Map 1 Map 2
- - - - 3876
0x87
(135)
1
0x13
(19)
187 35019 float
RWES
Pon.b
Pon.b
Special Output (1)
Input B Turn On
Compressor 2 power
on level.
-100.00 to 100.00% 0 Instance 1
Map 1 Map 2
- - - - 3878
0x87
(135)
1
0x14
(20)
188 35020 float
RWES
PoF.b
PoF.b
Special Output (1)
Input B Turn Off
Compressor 1 power
off level.
-100.00 to 100.00% 5 Instance 1
Map 1 Map 2
- - - - 3880
0x87
(135)
1
0x15
(21)
189 35021 float
RWES
on.t
on.t
Special Output (1)
Minimum On Time
At a minimum stay
on specified amount
of time.
0 to 9,999 seconds 20 Instance 1
Map 1 Map 2
- - - - 3882
0x87
(135)
1
0x16
(22)
190 35022 uint
RWES
oF.t
oF.t
Special Output (1)
Minimum Off Time
At a minimum
stay off specified
amount of time.
0 to 9,999 seconds 20 Instance 1
Map 1 Map 2
- - - - 3884
0x87
(135)
1
0x17
(23)
191 35023 uint
RWES
t.t
t.t
Special Output (1)
Valve Travel Time
The amount of time
it takes the valve to
fully open and then
fully close.
10 to 9,999 seconds 120 Instance 1
Map 1 Map 2
- - - - 3886
0x87
(135)
1
0x18
(24)
192 35024 uint
RWES
db
db
Special Output (1)
Dead Band
Output power needs
to change by speci-
fied level prior to
turning on.
1.0 to 100.0% 2 Instance 1
Map 1 Map 2
- - - - 3888
0x87
(135)
1
0x19
(25)
193 35025 float
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set