Watlow EZ-ZONE
®
PMI Controller 141 Chapter 6 Setup Page
Setup Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP -
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter
ID
Data
Type
and
Access
**
Fn
Fn
Function Key (1 to
2)
Action Function
Program the EZ Key
to trigger an action.
Functions respond
to a level state
change or an edge
level change.
Note:
The Limit Reset
function is not
available in firm-
ware revision 11.0
and above.
nonE None (61)
r.En Remote Set
Point (216)
LЛЏr Limit Reset,
edge triggered (82)
usr.r User Set Re-
store, edge trig-
gered (227)
P.LoC Keypad Lock-
out, level triggered
(217)
ALЛЏ Alarm Reset,
edge triggered (6)
SiL Silence Alarms,
edge triggered (108)
AoF Control Loops
Off and Alarms to
Non-alarm State,
level triggered (220)
F.AL Force Alarm to
occur, level trig-
gered (218)
idLE Idle Set Point,
level triggered (107)
tUnE Tune, edge
triggered (98)
ЛЏAn Manual, level
triggered (54)
oFF Switch Control
Loop Off, level trig-
gered (90)
t.da TRU-TUNE+
®
Disable, level trig-
gered (219)
P.diS Profile Dis-
able, level triggered
(206)
P.hoL Profile Hold/
Resume, level trig-
gered (207)
ProF Start Profile,
edge triggered (196)
P.StS Profile Start/
Stop, level triggered
(208)
s.stp Start Step
(1077)
None Instance 1
Map 1 Map 2
1364 1604
Instance 2
Map 1 Map 2
1384 1624
0x6E
(110)
3 to 4
3
138 10003 uint
RWES
* These parameters/prompts are available in these menus with firmware revisions 11.0 and above.
** R: Read, W: Write, E: EEPROM, S: User Set