Watlow EZ-ZONE
®
PMI Controller • 161 • Chapter 7 Profiling Page
Profiling Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pa-
ram-
eter
ID
Data
Type
and
Access
**
P1
prof
Profiling Menu
p1 to
p4
Profile [1 to 4] Step
Select a step to edit or view.
1 to 10 [profile 1]
11 to 20 [profile 2]
21 to 30 [profile 3]
31 to 40 [profile 4]
- - - - - - - - - - - - - - - -
S.typ
S.typ
Step Type
Select a step type.
Note:
Prior to selecting the Step
Type consider whether or
not profiles will be based
on time or rate of change.
By default, profiles are
configured for Time ti.
Therefore, Rate will not
be available here. If it is
desired to base profiles on
rate of change, navigate
to the Setup Page and then
the Global Menu where
Ramping Type can be
changed from Time to Rate.
UStP Unused Step
(50)
SoAH Soak (87)
ФІ.E Wait For Event
(144)
ФІ.Pr Wait For Pro-
cess (209)
ФІ.bo Wait For Both
(210)
JL Jump (116)
End End (27)
CLoC Wait For Time
(1543)
ti Time (143)
ratE Rate (81)
Unused Instance 1
Map 1 Map 2
2570 4500
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
1
21001 uint
RWE
t.SP1
t.SP1
Step Type Parameters
Target Set Point Loop 1
When Step Type is Time or
Rate, enter the closed loop
set point for loop 1 to ramp
to for this step.
-1,999.000 to
9,999.000°F or
units
-1,128 to
5,537.000°C
0.0°F or
units
-18°C
Instance 1
Map 1 Map 2
2572 4502
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
2
21002 float
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other inter-
faces.
** R: Read, W: Write, E: EEPROM, S: User Set