Watlow EZ-ZONE
®
PMI Controller • 162 • Chapter 7 Profiling Page
Profiling Page
Display
Parameter Name
Description
Range Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Pa-
ram-
eter
ID
Data
Type
and
Access
**
t.SP2
t.SP2
Step Type Parameters
Target Set Point Loop 2
When Step Type is Time en-
ter the closed loop set point
for loop 2 to ramp to for this
step.
-1,999.000 to
9,999.000°F or
units
-1,128 to
5,537.000°C
0.0°F or
units
-18°C
Instance 1
Map 1 Map 2
- - - - 4554
Offset to
next in-
stance Map
2 equals
+100
0x79 (121)
1 to 40
0x1C (28)
21028 float
RWE
hoUr
hoUr
Step Type Parameters
Hours
Select the hours (plus Min-
utes and Seconds) for a
timed step.
0 to 9999
0 Instance 1
Map 1 Map 2
2574 4504
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
3
21003 uint
RWE
ЛЏin
Min
Step Type Parameters
Minutes
When Step Type is Time,
Soak, or Wait For Time enter
Minutes (plus Hours and Sec-
onds) for this step.
0 to 59
0 Instance 1
Map 1 Map 2
2576 4506
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
4
21004 uint
RWE
SEC
SEC
Step Type Parameters
Seconds
When Step Type is Time,
Soak, or Wait For Time enter
Seconds (plus Hours and Min-
utes) for this step.
0 to 59
0 Instance 1
Map 1 Map 2
2578 4508
Offset to
next in-
stance (Map
1 equals
+50, Map 2
equals +100)
0x79 (121)
1 to 40
5
21005 uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other inter-
faces.
** R: Read, W: Write, E: EEPROM, S: User Set