PMI Controller 230 • Chapter 11 Appendix
Indication Description Possible Cause(s) Corrective Action
Device Error
100
rEtn
Controller displays
internal malfunc-
tion message at
power up.
Controller defective
Sensor input over driven
Replace or repair control-
ler
Check sensors for ground
loops, reverse wiring or
out of range values.
Heater Error
h.Er
Heater Error Current through load is
above current trip set
point
Current through load is
below current trip set
point
Check that the load cur-
rent is proper. Correct
cause of over current
and/or ensure current
trip set point is correct.
Check that the load cur-
rent is proper. Correct
cause of undercurrent
and/or ensure current
trip set point is correct.
Current Error
C.Er
Load current incor-
rect.
Shorted solid-state or
mechanical relay
Open solid-state or me-
chanical relay
Current transformer load
wire associated to wrong
output
Defective current trans-
former or controller
Noisy electrical lines
Replace relay
Replace relay
Route load wire through
current transformer from
correct output, and go to
the
C.si
Source Output
Instance parameter (Set-
up Page, Current Menu)
to select the output that
is driving the load.
Replace or repair sensor
or controller
Route wires appropriate-
ly, check for loose con-
nections, add line filters
Menus inac-
cessible
Unable to access
sEt, opEr, fCty
or prof menus or
particular prompts
in Home Page
Security set to incorrect
level
Digital input set to lock-
out keypad
Custom parameters in-
correct
Check
LoC
settings in
Factory Page and enter
appropriate password in
ULoC
setting in Factory
Page
Change state of digital
input
Change custom param-
eters in Factory Page