PMI Controller 73 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
o.u
o.v
Linearization (1 to
2)
Output Value
View the value of
this function's out-
put.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3572
Instance 2
Map 1 Map 2
- - - - 3642
0x86
(134)
1 to 2
7
- - - -
34007 float
R
No Dis-
play
Linearization (1 to
2)
Error
View reported
cause for Linear-
ization output mal-
function.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - Instance 1
Map 1 Map 2
- - - - 3614
Instance 2
Map 1 Map 2
- - - - 3684
0x86
(134)
1 to 2
0x1C (28)
- - - -
34028 uint
R
Pu
opEr
Process Value Menu
Su.a
Su.A
Process Value (1 to
2)
Source Value A
View the value of
Source A.
Linearization 1 is
connected to Source
A of Process Value 1
Linearization 2 is
connected to Source
A of Process Value 2
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3310
Instance 2
Map 1 Map 2
- - - - 3380
0x7E (126)
1 to 2
0x10 (16)
- - - - 26016 float
R
Su.b
Su.b
Process Value (1 to
2)
Source Value B
View the value of
Source B.
Linearization 2 is
connected to Source
B of Process Value 1
Linearization 1 is
connected to Source
B of Process Value 2
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
- - - - Instance 1
Map 1 Map 2
- - - - 3312
Instance 2
Map 1 Map 2
- - - - 3382
0x7E (126)
1 to 2
0x11 (17)
- - - - 26017 float
R
** R: Read, W: Write, E: EEPROM, S: User Set