PMI Controller 81 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
No Dis-
play
Control Loop (1 to
2)
Loop Output Power
View the loop out-
put power.
-100.0 to 100.0 - - - -
Instance 1
Map 1 Map 2
1908 2388
Instance 2
Map 1 Map 2
1978 2458
0x97 (151)
1 to 2
0x0F (15)
- - - - 8033
float
R
aLЛЏ
opEr
Alarm Menu
a.Lo
A.Lo
Alarm (1 to 4)
Low Set Point
If Type (Setup
Page, Alarm Menu)
is set to:
Process - set the
process value that
will trigger a low
alarm.
Deviation - set the
span of units from
the set point that
will trigger a low
alarm. A negative
set point repre-
sents a value below
closed loop set
point. A positive set
point represents a
value above closed
loop set point.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
32.0°F
or units
0.0°C
Instance 1
Map 1 Map 2
1482 1882
Offset to
next instance
(Map 1)
equals +50
Offset to
next instance
(Map 2)
equals +60
0x6D
(109)
1 to 24
2
18
9002 float
RWES
** R: Read, W: Write, E: EEPROM, S: User Set