Watlow EZ-ZONE
®
PMI Controller 82 Chapter 5 Operations Page
Operations Page
Display
Parameter Name
Description
Range Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Pa-
ram-
eter
ID
Data
Type
and
Ac-
cess
**
a.hi
A.hi
Alarm (1 to 4)
High Set Point
If Type (Setup
Page, Alarm Menu)
is set to:
Process - set the
process value that
will trigger a high
alarm.
Deviation - set the
span of units from
the set point that
will trigger a low
alarm. A negative
set point repre-
sents a value below
closed loop set
point. A positive set
point represents a
value above closed
loop set point.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
300.0
°F or
units
150.0
°C
Instance 1
Map 1 Map 2
1480 1880
Offset to
next instance
(Map 1)
equals +50
Offset to
next instance
(Map 2)
equals +60
0x6D
(109)
1 to 4
1
19
9001 float
RWES
A.CLr
A.CLr
Alarm (1 to 4)
Clear Alarm
Write to this reg-
ister to clear an
alarm
CLr Clear (1003)
ignr Ignore (204)
- - - - Instance 1
Map 1 Map 2
1504 1904
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0D (13)
- - - -
9026
uint
W
A.sir
A.Sir
Alarm (1 to 4)
Silence Alarm
Write to this reg-
ister to silence an
alarm
siL Silence (1010)
Instance 1
Map 1 Map 2
1506 1906
Offset to
next instance
(Map1 1
equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0x0E (14)
- - - -
9027
uint
W
** R: Read, W: Write, E: EEPROM, S: User Set