Watlow EZ-ZONE
®
PM PID Controller 46 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`iP;3]
[ ip.3]
Linearization (1)
Input Point 3
Set the value that
will be mapped to
output 3.
-1,999.000 to 9,999.000 2.0 Always Instance 1
Map 1 Map 2
- - - - 3578
0x86 (134)
1
0xA (10)
161 float
RWES
[`oP;3]
[ op.3]
Linearization (1)
Output Point 3
Set the value that will
be mapped to input 3.
-1,999.000 to 9,999.000 2.0 Always Instance 1
Map 1 Map 2
- - - - 3598
0x86 (134)
1
0x14 (20)
162 float
RWES
[`iP;4]
[ ip.4]
Linearization (1)
Input Point 4
Set the value that
will be mapped to
output 4.
-1,999.000 to 9,999.000 3.0 Always Instance 1
Map 1 Map 2
- - - - 3581
0x86 (134)
1
0xB (11)
163 float
RWES
[`oP;4]
[ op.4]
Linearization (1)
Output Point 4
Set the value that will
be mapped to input 4.
-1,999.000 to 9,999.000 3.0 Always Instance 1
Map 1 Map 2
- - - - 3600
0x86 (134)
1
0x15 (21)
164 float
RWES
[`iP;5]
[ ip.5]
Linearization (1)
Input Point 5
Set the value that
will be mapped to
output 5.
-1,999.000 to 9,999.000 4.0 Always Instance 1
Map 1 Map 2
- - - - 3582
0x86 (134)
1
0xC (12)
165 float
RWES
[`oP;5]
[ op.5]
Linearization (1)
Output Point 5
Set the value that will
be mapped to input 5.
-1,999.000 to 9,999.000 4.0 Always Instance 1
Map 1 Map 2
- - - - 3602
0x86 (134)
1
0x16 (22)
166 float
RWES
[`iP;6]
[ ip.6]
Linearization (1)
Input Point 6
Set the value that
will be mapped to
output 6.
-1,999.000 to 9,999.000 5.0 Always Instance 1
Map 1 Map 2
- - - - 3584
0x86 (134)
1
0xD (13)
167 float
RWES
[`oP;6]
[ op.6]
Linearization (1)
Output Point 6
Set the value that will
be mapped to input 6.
-1,999.000 to 9,999.000 5.0 Always Instance 1
Map 1 Map 2
- - - - 3604
0x86 (134)
1
0x17 (23)
168 float
RWES
[`iP;7]
[ ip.7]
Linearization (1)
Input Point 7
Set the value that
will be mapped to
output 7.
-1,999.000 to 9,999.000 6.0 Always Instance 1
Map 1 Map 2
- - - - 3586
0x86 (134)
1
0xE (14)
169 float
RWES
[`oP;7]
[ op.7]
Linearization (1)
Output Point 7
Set the value that will
be mapped to input 7.
-1,999.000 to 9,999.000 6.0 Always Instance 1
Map 1 Map 2
- - - - 3606
0x86 (134)
1
0x18 (24)
170 float
RWES
[`iP;8]
[ ip.8]
Linearization (1)
Input Point 8
Set the value that
will be mapped to
output 8.
-1,999.000 to 9,999.000 7.0 Always Instance 1
Map 1 Map 2
- - - - 3588
0x86 (134)
1
0xF (15)
171 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set

Table of Contents