PM PID Controller • 48 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`Fil]
[ FiL]
Process Value (1)
Filter
Filtering smooths out
the output signal of
this function block.
Increase the time to
increase filtering.
0.0 to 60.0 seconds 0.0 Always Instance 1
Map 1 Map 2
- - - - 3330
0x7E (126)
1
0x1A (26)
- - - - float
RWES
[`dio]
[`Set]
Digital Input/
Output Menu
[`dir]
[ dir]
Digital Input/Output
(5 to 6)
Direction
Set this function to
operate as an input or
output.
[OtPt] Output (68)
[iCon] Input Dry Contact
(44)
[``in] Input Voltage (193)
Output Always Instance 1
Map 1 Map 2
1000 1120
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
1
82 uint
RWES
[``Fn]
[ Fn]
Digital Output (5 to 6)
Action Function
Select what function
will drive this output.
[`oFF] Off (62)
[lim] Limit (126)
[Ent;b] Profile Event Out
B (234)
[Ent;A] Profile Event Out
A (233)
[SoF;2] Special Function
Output 2 (1533)
[SoF;1] Special Function
Output 1 (1532)
[CooL] Cool Power, Con-
trol Loop (161)
[heat] Heat Power, Con-
trol Loop (160)
[ALM] Alarm (6)
Off Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1008 1128
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
1 to 2
5
83 uint
RWES
[``Fi]
[ Fi]
Digital Output (5 to 6)
Function Instance
Set the instance of
the function selected
above.
1 to 4 1 Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1010 1130
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
6
84 uint
RWES
[`o;Ct]
[ o.Ct]
Digital Output (5 to 6)
Control
Set the output control
type. This parameter
is only used with PID
control, but can be set
anytime.
[`Ftb] Fixed Time Base
(34)
[`utb] Variable Time
Base (103)
Fixed
Time
Base
Direction is
set to Out-
put.
Instance 1
Map 1 Map 2
1002 1122
Offset to next
instance (Map
1 & Map 2)
equals +30
0x6A (106)
5 to 6
2
85 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set