Watlow EZ-ZONE
®
PM PID Controller • 60 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[R;typ]
[R.tyP]
Profile
Ramping Type
[rate] Rate (81)
[``ti] Time (143)
Time Always Instance 1
Map 1 Map 2
- - - - 4414
0x7A (122)
1
26 (38)
- - - - uint
RWE
[P;typ]
[P.tyP]
Profile
Profile Type
Set the profile startup
to be based on a set
point or a process
value.
[StPt] Set Point (85)
[`Pro] Process (75)
Set Point Always Instance 1
Map 1 Map 2
2534 4354
0x7A (122)
1
8
- - - - uint
RWE
[`GSE]
[ gSE]
Profile
Guaranteed Soak
Enable
Enables the guaran-
teed soak deviation
function in profiles.
[`oFF] Off (62)
[``on]
On (63)
Off Always Instance 1
Map 1 Map 2
2530 4350
0x7A (122)
1
6
- - - - uint
RWE
[GSd1]
[gSd1]
Profile
Guaranteed Soak
Deviation 1
Set the value of the
deviation band that
will be used in all
profile step types. The
process value must
enter the deviation
band before the step
can proceed.
0.0to9,999.000°Forunits
0.0to5,555.000°C
10.0°For
units
6.0°C
Always Instance 1
Map 1 Map 2
2532 4352
0x7A (122)
1
7
- - - - float
RWE
[`Si;a]
[ Si.a]
Profile Event Input
Source Instance A
Set the source for
WE1..
5 to 6 1 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 4390
0x7A (122)
1
0x1A (26)
- - - - uint
RWES
[`Si;B]
[ Si.b]
Profile Event Input
Source Instance B
Set the source for
WE2..
5 to 6 1 Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - - 4392
7A (122)
1
0x1B (27)
- - - - uint
RWES
[CoM]
[`SEt]
Communications Menu
PCoL]
[PCoL]
Communications 1
Protocol
Set the protocol of this
controller to the proto-
col that this network
is using.
[`Std] Standard Bus
(1286)
[Mod] Modbus RTU
(1057)
Modbus Always if
digit 8 is a
"1".
Instance 1
Map 1 Map 2
2492 2972
0x96 (150)
1
7
- - - - uint
RWE
`Ad;S]
[ Ad.S]
Communications 1
Address Standard
Bus
Set the network ad-
dress of this control-
ler. Each device on the
network must have a
unique address.
The Zone Display on
the front panel will
display this number.
1 to 16 1 Protocol
is set to
Standard-
bus.
Instance 1
Map 1 Map 2
2480 2960
0x96 (150)
1
1
- - - - uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set