EasyManua.ls Logo

Watlow Ez-Zone PM4 - Page 68

Default Icon
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watlow EZ-ZONE
®
PM PID Controller 65 Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter name
Description
Range Default Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Data
Type
&
Read/
Write
[~SEC]
[ SEC]
Step Type Parameters
Seconds
Select the seconds (plus
Hours and Minutes) for a
timed step.
0 to 59
0 Step Type is
set to Time or
Soak.
Instance 1
Map 1 Map 2
2578 4508
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
5
uint
RWE
W;P1]
[W.P1]
Step Type Parameters
Wait For Process Value
Select which analog input
Wait For Process will use.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
0.0°For
units
-18.0°C
Step Type is
set to Wait For
Process.
Instance 1
Map 1 Map 2
2590 4520
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xB (11)
float
RWE
WE;1]
[WE.1]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2586 4516
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
9
uint
RWE
[WE;2]
[WE.2]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2588 4518
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xA (10)
uint
RWE
[dow]
[dow]
Step Type Parameters
Day of Week
[``ed] Every Day (1567)
[`wd] Week days (1566)
[`sun] Sunday (1565)
[mon] Monday (1559)
[`tue] Tuesday (1560)
[wed] Wednesday (1561)
[thUr] Thursday (1562)
[`fri] Friday (1563)
[`sat] Saturday (1564)
Sunday If real time
clock is present
and StepType
is set to Wait
for Time.
Instance 1
Map 1 Map 2
- - - - 4580
Offset to next
instance Map 2
equals +100)
0x79 (121)
1 to 40
0x29 (41)
uint
RWE
[~~JS]
[ JS]
Step Type Parameters
Jump Step
Select a step to jump to.
1 to 40
0 Step Type is
set to Jump
Loop.
Instance 1
Map 1 Map 2
2592 4522
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xC (12)
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User Set