Watlow EZ-ZONE
®
PM PID Controller 32 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
Linearization (1)
Output Error
View reported cause
for Linearization out-
put malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
Instance 1
Map 1 Map 2
- - - - 3614
0x86 (134)
1
0x1C (28)
- - - - uint
R
[``Pu]*
[oPEr]
Process Value Menu
[`Su;A]
[ Sv.A]
Process Value (1)
Source Value A
View the value of
Source A.
Linearization 1 is con-
nected to Source A of
Process Value 1
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
Always if
part number
digit 3 is C,
R, J, B, E
or N.
PM8 and 9
only
Instance 1
Map 1 Map 2
- - - - 3310
0x7E (126)
1
0x10 (16)
float
R
[oFSt]
[oFSt]
Process Value (1)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0 Always Instance 1
Map 1 Map 2
- - - - 3324
0x7E (126)
1
0x17 (23)
- - - - float
RWES
[``o;u]
[ o.v]
Process Value (1)
Output Value
View the value of this
function block's output.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
Always Instance 1
Map 1 Map 2
- - - - 3322
0x7E (126)
1
0x16 (22)
- - - - float
R
Process Value (1)
Output Error
View reported cause
for Process output
malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
Instance 1
Map 1 Map 2
- - - - 3332
0x86 (134)
1 to 2
0x1B (27)
- - - - uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other inter- faces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EEPROM
S: User
Set

Table of Contents