PM PID Controller 58 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`A;Si]
[ A.Si]
Alarm (1 to 4)
Silencing
Turn alarm silencing
on to allow the user to
disable this alarm.
[`oFF] Off (62)
[``on] On (63)
Off Type is not
set to Off.
Instance 1
Map 1 Map 2
1490 1890
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
6
29 uint
RWES
[A;dSP]
[A.dSP]
Alarm (1 to 4)
Display
Display an alarm
message when an
alarm is active.
[`oFF] Off (62)
[``on] On (63)
On Type is not
set to Off.
Instance 1
Map 1 Map 2
1510 1910
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
0x10 (16)
30 uint
RWES
[`A;dL]
[ A.dL]
Alarm (1 to 4)
Delay
Set the span of time
that the alarm will be
delayed after the pro-
cess value exceeds the
alarm set point.
0 to 9,999 seconds 0 Type is not
set to Off.
Instance 1
Map 1 Map 2
1520 1920
Offset to next
instance (Map
1 equals +50,
for Map 2
equals +60)
0x6D (109)
1 to 4
0x15 (21)
31 uint
RWES
[`FUn]
[`Set]
`leu]
[ LEv]
Function Key (1 to 2)
Level
The Function Key will
always power up in
the low state.
Pressing the Function
Key will toggle the
selected action.
high] High (37)
[Low] Low (53)
High Always Instance 1
Map 1 Map 2
1320 1560
Instance 2
Map 1 Map 2
1340 1580
0x6E (110)
1 to 2
1
137 uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set