Watlow EZ-ZONE
®
PM PID Controller • 37 • Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
Alarm (1 to 4)
Alarm State
Current state of
alarm
Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)
No param-
eter
Instance 1
Map 1 Map 2
1496 1896
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
9
- - - - uint
R
Alarm (1 to 4)
Alarm Clearable
Current state of
alarm
[``no] No (59)
[`YES] Yes (106)
No param-
eter
Instance 1
Map 1 Map 2
1502 1902
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xC (12)
- - - - uint
R
Alarm (1 to 4)
Alarm Clear Re-
quest
Write to this register
to clear an alarm
0 No param-
eter
Instance 1
Map 1 Map 2
1504 1904
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xD (13)
- - - - uint
W
Alarm (1 to 4)
Alarm Silence Re-
quest
Write to this register
to silence an alarm
0 No param-
eter
Instance 1
Map 1 Map 2
1506 1906
Offset to next
instance (Map1
1 equals +50,
Map 2 equals
+60)
0x6D
(109)
1 to 4
0xE (14)
- - - - uint
W
[P;Sta]
[oPEr]
Profile Status Menu
Profile Menu appears if:
(PM _ [R, B*, N, E*] _ _ _-_ _ _ _ _ _ _)
* Available with PM8/9 only
* Some parameters in the Profile Status Menu can be changed for the currently running profile, but should only be changed by knowl-
edgeable personnel and with caution. Changing parameters via the Profile Status Menu will not change the stored profile but will
have an immediate impact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be saved and will also have an immediate impact on the running pro-
file.
[P;Str]
[P.Str]
Profile Status
Profile Start
Select step to act
upon.
1 to 40 1 Always Instance 1
Map 1 Map 2
2520 4340
0x7A (122)
1
1
204 uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other inter- faces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EEPROM
S: User
Set