Watlow EZ-ZONE
®
PM PID Controller • 45 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`FiL]
[ FiL]
Analog Input (1)
Filter
Filtering smooths out
the process signal to
both the display and
the input. Increase
the time to increase
filtering.
0.0 to 60.0 seconds 0.5 Always Instance 1
Map 1 Map 2
386 386
0x68 (104)
1
0xE (14)
12 float
RWES
[`i;Er]
[ i.Er]
Analog Input (1)
Error Latching
Turn input error
latching on or off. If
latching is on, errors
must be manually
cleared.
[`off] Off (62)
[``on] On (63)
Off Always Instance 1
Map 1 Map 2
414 414
0x68 (104)
1
0x1C (28)
- - - - uint
RWES
[`Lnr]*
[`Set]
Linearization Menu
[``Fn]
[ Fn]
Linearization (1)
Function
Set how this function
will linearize Source
A which is Analog
Input 1.
[`oFF] Off (62)
[intr] Interpolated (1482)
Off Always if
part num-
ber digit 4
is C, R, J, B,
E or N.
PM8 and 9
only
Instance 1
Map 1 Map 2
- - - - 3568
0x86 (134)
1
5
155 uint
RWES
[Unit]
[Unit]
Linearization (1)
Units
Set the units of
Source A which is
Analog Input 1.
[nonE] None (61)
[`Src] Source (1539)
[``rh] Relative Humidty
(1538)
[`pro] Process (75)
[PWr] Power (73)
[`r;tp] Relative Tempera-
ture (1541)
[`A;tP] Absolute Tempera-
ture (1540)
Source Always Instance 1
Map 1 Map 2
- - - - 3616
0x86 (134)
1
0x29 (41)
156 uint
RWES
[`iP;1]
[ ip.1]
Linearization (1)
Input Point 1
Set the value that
will be mapped to
output 1.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3574
0x86 (134)
1
8
157 float
RWES
[`oP;1]
[ op.1]
Linearization (1)
Output Point 1
Set the value that will
be mapped to input 1.
-1,999.000 to 9,999.000 0.0 Always Instance 1
Map 1 Map 2
- - - - 3594
0x86 (134)
1
0x12 (18)
158 float
RWES
[`iP;2]
[ ip.2]
Linearization (1)
Input Point 2
Set the value that
will be mapped to
output 2.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3576
0x86 (134)
1
9
159 float
RWES
[`oP;2]
[ op.2]
Linearization (1)
Output Point 2
Set the value that will
be mapped to input 2.
-1,999.000 to 9,999.000 1.0 Always Instance 1
Map 1 Map 2
- - - - 3597
0x86 (134)
1
0x13 (19)
160 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set