Watlow EZ-ZONE
®
PM PID Controller 61 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[Ad;M]
[Ad.M]
Communications (1)
Address Modbus
Set the network ad-
dress of this control-
ler. Each device on the
network must have a
unique address.
1 to 247 1 Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2482 2962
0x96 (150)
1
2
- - - - uint
RWE
[bAUd]
[bAUd]
Communications (1)
Baud Rate Modbus
Set the speed of this
controller's communi-
cations to match the
speed of the serial
network.
9,600 (188)
19,200 (189)
38,400 (190)
9,600 Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2484 2964
0x96 (150)
1
3
- - - - uint
RWE
[`PAr]
[ PAr]
Communications
Parity Modbus (1)
Set the parity of this
controller to match
the parity of the serial
network.
[none] None (61)
[EuEn] Even (191)
[`odd] Odd (192)
None Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2486 2966
0x96 (150)
1
4
- - - - uint
RWE
[M;hL]
[M.hL]
Communications (1)
Modbus Word Order
Select the word or-
der of the two 16-bit
words in the floating-
point values.
[Lohi] Low-High (1331)
[hiLo] High-Low (1330)
Low-High Protocol
is set to
Modbus.
Instance 1
Map 1 Map 2
2488 2968
0x96 (150)
1
5
- - - - uint
RWE
[Map]
[ Map]
Communications (1)
Data Map
If set to 1 the control
will use PM legacy
mapping. If set to 2
the control will use
new mapping to ac-
commodate new func-
tions.
1 to 2 1 Always - - - -
[`nU;S]
[ nV.S]
Communications (1)
Non-volatile Save
If set to Yes all values
written to the control
will be saved in EE-
PROM.
[`yes] Yes (106)
[``no] No (59)
Yes Always Instance 1
Map 1 Map 2
2494 2974
0x96 (150)
1
8
198 uint
RWE
[rtC]*
[`SEt]
Real Time Clock Menu
[hoUr]
[hoUr]
Real Time Clock
Hours
0 to 23 0 Always if
4th digit
in part
number is
a "B" or
"E".
Instance 1
Map 1 Map 2
- - - - 4004
88 (136)
1
3
- - - - uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.