Watlow EZ-ZONE
®
PM PID Controller • 65 • Chapter 7 Profiling Page
Profiling Page
Dis-
play
Parameter name
Description
Range Default Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Data
Type
&
Read/
Write
[~SEC]
[ SEC]
Step Type Parameters
Seconds
Select the seconds (plus
Hours and Minutes) for a
timed step.
0 to 59
0 Step Type is
set to Time or
Soak.
Instance 1
Map 1 Map 2
2578 4508
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
5
uint
RWE
W;P1]
[W.P1]
Step Type Parameters
Wait For Process Value
Select which analog input
Wait For Process will use.
-1,999.000to9,999.000°F
or units
-1,128.000to5,537.000°C
0.0°For
units
-18.0°C
Step Type is
set to Wait For
Process.
Instance 1
Map 1 Map 2
2590 4520
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xB (11)
float
RWE
WE;1]
[WE.1]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2586 4516
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
9
uint
RWE
[WE;2]
[WE.2]
Step Type Parameters
Wait Event (5-6)
Select the event state that
must be satisfied during
this step. Digital input 5
provides the state of Event
1, and digital input 6 pro-
vides the state of Event 2.
[`oFF] Off (62)
[``on] On (63)
[nonE] None (61)
Off Step Type is
set to Wait
Event or Wait
for Both.
Instance 1
Map 1 Map 2
2588 4518
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xA (10)
uint
RWE
[dow]
[dow]
Step Type Parameters
Day of Week
[``ed] Every Day (1567)
[`wd] Week days (1566)
[`sun] Sunday (1565)
[mon] Monday (1559)
[`tue] Tuesday (1560)
[wed] Wednesday (1561)
[thUr] Thursday (1562)
[`fri] Friday (1563)
[`sat] Saturday (1564)
Sunday If real time
clock is present
and StepType
is set to Wait
for Time.
Instance 1
Map 1 Map 2
- - - - 4580
Offset to next
instance Map 2
equals +100)
0x79 (121)
1 to 40
0x29 (41)
uint
RWE
[~~JS]
[ JS]
Step Type Parameters
Jump Step
Select a step to jump to.
1 to 40
0 Step Type is
set to Jump
Loop.
Instance 1
Map 1 Map 2
2592 4522
Offset to next
instance (Map
1 equals +50,
Map 2 equals
+100)
0x79 (121)
1 to 40
0xC (12)
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.
R: Read
W: Write
E:
EEPROM
S: