Watlow EZ-ZONE
®
PM PID Controller 70 Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[roll]
[roLL]
Security Setting
Rolling Password
When power is
cycled a new Public
Key will be dis-
played.
[`off] Off
[``on] On
Off Always - - - - - - - - - - - - - - - -
[pas;u]
[PAS.u]
Security Setting
User Password
Used to acquire ac-
cess to menus made
available through
the Locked Access
Level setting.
10 to 999
63 Always - - - - - - - - - - - - - - - -
[pas;a]
[PAS.A]
Security Setting
Administrator
Password
Used to acquire full
access to all menus.
10 to 999
156 Always - - - - - - - - - - - - - - - -
[ULoC]
[FCty]
Security Setting Menu
[Code]
[CodE]
Security Setting
Public Key
If Rolling Password
turned on, generates
a random number
when power is
cycled. If Rolling
Password is off fixed
number will be dis-
played.
Customer Specific
0 Always - - - - - - - - - - - - - - - -
[pass]
[PASS]
Security Setting
Password
Number returned
from calculation
found in Features
section under Pass-
word Security.
-1999 to 9999
0 Always - - - - - - - - - - - - - - - -
[diag]
[fcty]
Diagnostics Menu
[``Pn]
[ Pn]
Diagnostics Menu
Part Number
Display this control-
ler's part number.
15 characters Instance 1
only
0x65 (101)
1
9
115 string
RWE
[`rEu]
[ rEu]
Diagnostics Menu
Software Revision
Display this control-
ler's firmware revi-
sion number.
1 to 10 Always 0x65 (101)
1
0x11 (17)
116 string
R
[S;bLd]
[S.bLd]
Diagnostics Menu
Software Build
Number
Display the firm-
ware build number.
0 to 2,147,483,647 Always Instance 1
Map 1 Map 2
8 8
0x65 (101)
1
5
- - - - dint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
If there is only one instance of a menu, no submenus will appear.
R: Read
W: Write
E:
EEPROM
S:
User