36 BlueCool S-Series
14.2.3 Parameter list, setting level 3 (Parameter menu)
Parameter Meaning Unit / pa-
rameter
Value range Factory
setting
See
Page
Setting level 3
Compressor
switching points
Min. switch-off temperature cool-
ing
Switch-off temperature cooling
Switch-on temperature cooling
Switch-off temperature heating
Switch-on temperature heating
Hysteresis
First switch-on delay
Max. duration shortfall
°C (°F)
°C (°F)
°C (°F)
°C (°F)
°C (°F)
°C (°F)
sec.
sec.
-4 to 15 (24 to 59)
-4 to 15 (24 to 59)
2 to 18 (36 to 64)
30 to 55 (86 to 131)
27 to 50 (81 to 122)
0,1 to 0,8 (0,2 to 1,4)
01 to 200
000 to 999
-4 °C / 25 °F
-2 °C / 28 °F
4 °C / 39 °F
52 °C / 126 °F
48 °C / 118 °F
0,8 °C / 1,4 °F
10
600
page
20
Fan settings Fan type
Continuous fan operation
Fan speed 5
Fan speed 4
Fan speed 3
Fan speed 2
Fan speed 1
-
-
-
-
-
-
-
AC, EC, electronic silencer
On/Off
30 - 100
30 - 100
30 - 100
30 - 100
30 - 100
AC
Off
100 (50Hz)
100 (60Hz)
58 (50Hz)
69 (60Hz)
49 (50Hz)
60 (60Hz)
41 (50Hz)
53 (60Hz)
35 (50Hz)
45 (60Hz)
page
20
Further settings Access code
Undervoltage switch-off
Correction cabin temperature sen-
sor K or °F
CAN-bus address
Factory setting
-
V
°C (°F)
00 = entry of access code not neces-
sary to access setting level 3. 01 to
99 = Access code activated.
180 - 210 (230 V)
90 - 105 (115 V)
-5.5 to 5.5 / -9.9 to 9.9
1 to 239
Reset
64
195 (230 V)
97 (115 V)
0
-
-