What to do if Weishaupt WTC-GB 90-A Boiler shows warning code W12?
- BbooneconnieJul 31, 2025
If your Weishaupt Boiler displays warning code W12, it indicates that the temperature at eSTB exceeds 95 °C, the temperature at the supply sensor is above 95 °C, or the temperature at the return sensor is above 95 °C. To resolve this, you should: * Check the water flow. * Verify the functionality of the pumps. * Examine parameter A32. * Vent the boiler on the water side.