Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 104/226 © Woodward
ID
Parameter
CL
Setting range
Format
Description
7710
Reactive
load control
mode
-
Off /
Inactive /
Droop /
VAR sharing /
VAR control /
PF control
-
Display of the different
Reactive load control modes
:
Off: The reactive load control mode is disabled.
Inactive: The reactive load control is not active.
Droop: The reactive load control runs in droop or droop tracking.
VAR sharing: The reactive load sharing is active.
VAR control: The reactive load control with kvar reference is ac-
tive.
PF control: The reactive load control with power factor reference
is active.
4603
Load control
mode
- Droop /
At Unload Trip /
Base Load /
Base Load
Ramp /
Base Load
Lower /
Base Load
Raise /
Load share
unload /
Load share
Ramp /
Load sharing /
Base Load
Unload /
Process Ramp /
Process Control /
Process Lower /
Process Raise /
Inactive
- Display of the different Load control modes:
Droop: The Load control runs in droop or droop tracking.
At Unload Trip: The Load control or the load share control re-
sides in unloaded condition.
Base Load: The Load control runs in base load.
Base Load Ramp: The Load control ramps to a reference value.
Base Load Lower: A base load lower command is active.
Base Load Raise: A base load raise command is active.
Load share unload: The load sharing unloads the generator and
the GCB will be opened.
Load share Ramp: The load sharing loads the generator.
Load sharing: The load sharing mode is active.
Base Load Unload: The load control unloads the generator.
Process Ramp: The generator is ramped to the process control
reference.
Process Control: The process control mode is active.
Process Lower: A process reference lower command is active.
Process Raise: A process reference raise command is active.
Inactive: The load control is inactive.
7721
Load
reference
-
Info
0.0 kW
Display of Load control reference in kW.
This field indicates the momentarily load control setpoint.
4605
Process
reference
- Info
0.0 % Display of process control reference in percentage.
This field indicates the momentarily process control setpoint.
7722
Reactive
load
reference
-
Info
0.0 kvar
Display of Reactive load reference in kvar.
This field indicates the momentarily reactive load control setpoint.
7708
Power factor
reference
-
Info
0.00
Display of the Power factor reference.
4606
Synchronizer
timeout
- Info
- / Alarm Display of Alarm: Synchronizer timeout.
4607
Sync reclose
limit
-
Info
- / Alarm
Display of Alarm: Synchronizer reclose limit.
4608
High load
limit
-
Info
- / Alarm
Display of Alarm: High load limit.
4609
Low load
limit
-
Info
- / Alarm
Display of Alarm: Low load limit.
4610
High process
limit
-
Info
- / Alarm
Display of Alarm: High process limit.
4611
Low process
limit
- Info
- / Alarm Display of Alarm: Low process limit.
4613
High voltage
limit
-
Info
- / Alarm
Display of Alarm: High voltage limit.
4612
Low voltage
limit
-
Info
- / Alarm
Display of Alarm: Low voltage limit.
4614
Voltage
range limit
-
Info
- / Alarm
Display of Alarm: Voltage range limit.
4615
Communica-
tion error
-
Info
- / Alarm
Display of Alarm: Communication error.