Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 104/226 © Woodward
Inactive /
Droop /
VAR sharing /
VAR control /
PF control
Reactive load control modes
Off: The reactive load control mode is disabled.
Inactive: The reactive load control is not active.
Droop: The reactive load control runs in droop or droop tracking.
VAR sharing: The reactive load sharing is active.
VAR control: The reactive load control with kvar reference is ac-
tive.
PF control: The reactive load control with power factor reference
mode
- Droop /
At Unload Trip /
Base Load /
Base Load
Ramp /
Base Load
Lower /
Base Load
Raise /
Load share
unload /
Load share
Ramp /
Load sharing /
Base Load
Unload /
Process Ramp /
Process Control /
Process Lower /
Process Raise /
Inactive
- Display of the different Load control modes:
Droop: The Load control runs in droop or droop tracking.
At Unload Trip: The Load control or the load share control re-
sides in unloaded condition.
Base Load: The Load control runs in base load.
Base Load Ramp: The Load control ramps to a reference value.
Base Load Lower: A base load lower command is active.
Base Load Raise: A base load raise command is active.
Load share unload: The load sharing unloads the generator and
the GCB will be opened.
Load share Ramp: The load sharing loads the generator.
Load sharing: The load sharing mode is active.
Base Load Unload: The load control unloads the generator.
Process Ramp: The generator is ramped to the process control
reference.
Process Control: The process control mode is active.
Process Lower: A process reference lower command is active.
Process Raise: A process reference raise command is active.
Inactive: The load control is inactive.
Display of Load control reference in kW.
This field indicates the momentarily load control setpoint.
0.0 % Display of process control reference in percentage.
This field indicates the momentarily process control setpoint.
Display of Reactive load reference in kvar.
This field indicates the momentarily reactive load control setpoint.
Display of the Power factor reference.
- / Alarm Display of Alarm: Synchronizer timeout.
Display of Alarm: Synchronizer reclose limit.
Display of Alarm: High load limit.
Display of Alarm: Low load limit.
Display of Alarm: High process limit.
- / Alarm Display of Alarm: Low process limit.
Display of Alarm: High voltage limit.
Display of Alarm: Low voltage limit.
Display of Alarm: Voltage range limit.
Display of Alarm: Communication error.