Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 111/226
Overview Pages
The DSLC-2 provides finally 3 overview pages showing information from up to 32 DSLC-2 and up to
16 MSLC-2.
DSLC-2 Overview Page 1
The DSLC-2 overview page 1 informs about the conditions of the DSLC-2 number 1 to 16 connected to the net-
work. This helps for commissioning a DSLC-2 / MSLC-2 system.
Figure 3-39: ToolKit DSLC-2 overview page 1
ID
Parameter
CL
Setting range
Default
Description
GCB
feedback
- Open / Closed - This field indicates the GCB state of the DSLC-2 unit 1 to 16.
Sync control
state
-
Off /
Check /
Permissive /
Run /
Close Timer /
Sync Timer /
Synchronized /
Auto-Off
-
This field indicates the Synchronizer control state of DSLC-2 unit
1 to 16:
Off: The synchronizer is not active.
Check: The synchronizer runs in check mode.
Permissive: The synchronizer runs in permissive mode.
Run: The synchronizer is full active.
Close Timer: This is the GCB close command.
Sync Timer: The synchronizer is stopped, because of a sync
time-out.
Synchronized: The GCB is closed.
Auto-Off: The synchronizer is stopped, because of an unsuccess-
ful closure of the GCB. (resync is disabled).