Woodward DSLC-2 - Table 3-30: Parameter - DSLC-2 Overview Page 3 - MSLC-2

Woodward DSLC-2
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 116/226 © Woodward
ID
Parameter
CL
Setting range
Default
Description
React load
control state
-
Off /
Inactive /
Off Line /
Voltage Control /
Reactive Load
Control /
Export/Import
Control /
Constant Gen PF
Control
-
This field indicates the
Reactive load control
state of MSLC-2 unit
33 to 48.
Off: No information received.
Inactive: The reactive load control mode is inactive.
Off Line: The reactive load control is inactive.
Voltage Control: Voltage control during synchronization.
Reactive Load Control: Reactive load control through MSLC-2.
Export/Import Control: Reactive Export/Import control through
MSLC-2.
Constant Gen PF Control: Generator constant power factor con-
trol through MSLC-2.
Real load
control state
-
Off /
Inactive /
Offline /
Frequency
Control /
Baseload /
Import/Export
Control /
Process Control /
Remote Process
-
This field indicates the Real load control state of MSLC-2 unit 33
to 48.
Off: No information received.
Inactive: The load control mode is inactive.
Off Line: The load control mode is off.
Frequency Control: Frequency control during synchronization.
Baseload: Load control through MSLC-2.
Export/Import Control: Export/import control [kW] through
MSLC-2.
Process Control: Process control through MSLC-2.
Remote Process: Remotely guided process control through
MSLC-2. Analog input for process reference used.
Auto
segment
number
-
1 to 8
-
Display of
Auto segment number
of MSLC-2 unit 33 to 48.
Unit id
available
-
Yes / No
-
Display if Unit Id available or not of MSLC-2 unit 33 to 48.
Table 3-30: Parameter DSLC-2 overview page 3 MSLC-2