Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 188/226 © Woodward
Visualization
The visualization over Modbus is provided in a very fast data protocol where important system data like alarm
states, AC measurement data, switch states and various other information may be polled. According to the
DSLC-2 / MSCL-2 Modbus addressing range, the visualization protocol can be reached on addresses starting at
450001. On this address range it is possible to do block reads from 1 up to 128 Modbus registers at a time.
The following ModScan32 screenshot shows the configurations made to read the visualization protocol with a
block read of 128 registers.
Figure 10-2: Modbus - visualization configurations