Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 188/226 © Woodward
Visualization
The visualization over Modbus is provided in a very fast data protocol where important system data like alarm
states, AC measurement data, switch states and various other information may be polled. According to the
DSLC-2 / MSCL-2 Modbus addressing range, the visualization protocol can be reached on addresses starting at
450001. On this address range it is possible to do block reads from 1 up to 128 Modbus registers at a time.
Modbus Read
Addresses
Description
Multiplier
Units
450001
Protocol-ID, always 5200
--
450002
Scaling power
--
............
.........
.....
.....
............
.........
.....
.....
............
.........
.....
.....
............
.........
.....
.....
450171
Remote load reference
input
0.1
kW
Table 10-3: Modbus - address range block read
NOTE
Table 10-3 is only an excerpt of the data protocol. It conforms to the data protocol 5200 that is also
used by Ethernet. Refer to Data Protocol 5200on page 206 for the complete protocol.
The following ModScan32 screenshot shows the configurations made to read the visualization protocol with a
block read of 128 registers.
Figure 10-2: Modbus - visualization configurations