Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 196/226 © Woodward
Changing Parameter Settings Via Modus
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Parameter Setting
The example tables below are excerpts of the parameter list in Chapter: “Configuration & Operation“.
Be sure to enter the password for code level 2 or higher for the corresponding interface to get access
for changing parameter settings.
The new entered value must comply with the parameter setting range when changing the parameter
Example 1: Addressing the password for serial interface1:
Password for serial interface1
Table 10-9: Modbus – password for serial interface 1
Modbus address = 400000 + (Par. ID + 1) = 410402
Modbus length = 1 (UNSIGNED 16)
The following Modscan32 screenshots show the configurations made to address parameter 10401.
Figure 10-7: Modbus - configuration example 1