Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 197/226
Example 2: Addressing the generator rated voltage:
1766 Generator rated voltage 50 to 650000 V UNSIGNED 32
Table 10-10: Modbus – generator rated voltage
Modbus address = 40000 + (Par. ID + 1) = 41767
Modbus length = 2 (UNSIGNED 32)
The following Modscan32 screenshot shows the configurations made to address parameter 1766.
Figure 10-8: Modbus - configuration example 2
Example 3: Addressing the generator voltage measuring:
Generator voltage measuring
Table 10-11: Modbus – generator voltage measuring
Modbus address = 40000 + (Par. ID + 1) = 41852
Modbus length = 1 (UNSIGNED 16)
If the setting range contains a list of parameter settings like in this example, the parameter settings are
numbered and start with 0 for the first parameter setting. The number corresponding with the respec-
tive parameter setting must be configured.
The following Modscan32 screenshot shows the configurations made to address parameter 1851, which is confi-
gured to "3Ph 4W".
Figure 10-9: Modbus - configuration example 3