Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 206/226 © Woodward
Appendix C.
Data Protocols
Data Protocol 5200
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Modbus
Adress
Modicon
Adress
Size
Format
Parameter
ID
Description DSLC-2
Multiplier
(BUS-data * Multiplier = real
value)
Units
50000
450001
16 bits
signed
Protocol-ID, always 5200
--
50001
450002
16 bits
signed
3181
Scaling Power (16 bits)
Exponent 10
x
W (5;4;3;2)
50002
450003
16 bits
signed
3182
Scaling Volts (16 bits) Ex-
ponent 10
x
V (2;1;0;-1)
50003
450004
16 bits
signed
3183
Scaling Amps (16 bits) Ex-
ponent 10
x
A (0;-1)
50004
450005
16 bits
signed
7732
Scaling Process enginee-
ring unit
50005
450006
16 bits
0 (reserve)
50006
450007
16 bits
0 (reserve)
50007
450008
16 bits
0 (reserve)
50008
450009
16 bits
0 (reserve)
50009
450010
16 bits
0 (reserve)
AC Measurement values
50010
450011
16 bits
signed
144
Generator frequency
0.01
Hz
50011
450012
16 bits
signed
246
Generator total power
scaled defined by index 3181
(modicon Adress 450002)
kW
50012
450013
16 bits
signed
247
Generator total reactive
power
scaled defined by index 3181
(modicon Adress 450002)
kvar
50013
450014
16 bits
signed
160
Generator power factor
0.001
50014
450015
16 bits
signed
248
Generator voltage L1-L2
scaled defined by index 3182
(modicon Adress 450003)
V
50015
450016
16 bits
signed
249
Generator voltage L2-L3
scaled defined by index 3182
(modicon Adress 450003)
V
50016
450017
16 bits
signed
250
Generator voltage L3-L1
scaled defined by index 3182
(modicon Adress 450003)
V
50017
450018
16 bits
signed
251
Generator voltage L1-N
scaled defined by index 3182
(modicon Adress 450003)
V
50018
450019
16 bits
signed
252
Generator voltage L2-N
scaled defined by index 3182
(modicon Adress 450003)
V
50019
450020
16 bits
signed
253
Generator voltage L3-N
scaled defined by index 3182
(modicon Adress 450003)
V
50020
450021
16 bits
signed
255
Generator current 1
scaled defined by index 3183
(modicon Adress 450004)
A
50021
450022
16 bits
signed
256
Generator current 2
scaled defined by index 3183
(modicon Adress 450004)
A
50022
450023
16 bits
signed
257
Generator current 3
scaled defined by index 3183
(modicon Adress 450004)
A
50023
450024
16 bits
signed
209
Busbar frequency
0.01
Hz
50024
450025
16 bits
signed
254
Busbar voltage L1-L2 (or
L1-N)
scaled defined by index 3182
(modicon Adress 450003)
V
50025
450026
16 bits
signed
147
Auxiliary busbar frequency
0.01
Hz
50026
450027
16 bits
signed
118
Auxiliary busbar voltage
L1-L2
scaled defined by index 3182
(modicon Adress 450003)
V
50027
450028
16 bits
signed
119
Auxiliary busbar L2-L3
scaled defined by index 3182
(modicon Adress 450003)
V
50028
450029
16 bits
signed
120
Auxiliary busbar L3-L1
scaled defined by index 3182
(modicon Adress 450003)
V