EasyManua.ls Logo

Woodward DSLC-2 - Figure 2-11: Voltage Measuring - Generator Windings, 3 Ph 4 W; Figure 2-12: Voltage Measuring - Generator Measuring Inputs, 3 Ph 4 W; Table 2-5: Voltage Measuring - Terminal Assignment - Generator, 3 Ph 4 W

Woodward DSLC-2
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
© Woodward Page 29/226
Voltage Measuring: Generator, Parameter Setting '3Ph 4W' (3-phase, 4-wire)
Figure 2-11: Voltage measuring - generator windings, 3Ph 4W
Figure 2-12: Voltage measuring - generator measuring inputs, 3Ph 4W
3Ph 4W
Wiring terminals
Note
Rated voltage (range) [1] 120 V (50 to 130 V
eff.
) [4] 480 V (131 to 480 V
eff.
)
2
Measuring range (max.)
[1] 0 to 150 Vac
[4] 0 to 600 Vac
Figure
A
C
E
G
B
D
F
H
DSLC-2 terminal 29 31 33 35 30 32 34 36
Phase
L1 / AØ
L2 / BØ
L3 / CØ
N
L1 / AØ
L2 / BØ
L3 / CØ
N
Table 2-5: Voltage measuring - terminal assignment - generator, 3Ph 4W
2 For different voltage systems, different wiring terminals have to be used. Incorrect measurements are possible if both voltage systems use
the same N terminal.
L1
L2
N
L3
N
A1
A2
A
B
B2
B1
C
C2
C1
L1
L2
N
L3
N
A1
A2
A
B
C6
C5
B6
B5
A5
A6
B2
B1
C
C2
C1
L1
L2
N
L3
N
A1
A2
A
B
B6
B5
A5
A6
C
C6
C5
B2
B1
C2
C1

Table of Contents

Related product manuals