Manual 37443A DSLC-2 - Digital Synchronizer and Load Control
Page 32/226 © Woodward
Voltage Measuring: Busbar, Parameter Setting '1Ph 2W' (1-phase, 2-wire)
NOTE
The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note to
configure and wire the DSLC-2 consistently. Refer to the chapter Configuration & Operation.
'1Ph 2W' Phase-Neutral Measuring
Figure 2-16: Voltage measuring - busbar measuring inputs, 1Ph 2W (phase-neutral)
1Ph 2W
Wiring terminals
Note
Rated voltage (range)
[1] 100 V (50 to 130 V
eff.
)
[4] 400 V (131 to 480 V
eff.
)
4
Measuring range (max.)
[1] 0 to 150 Vac
[4] 0 to 600 Vac
Figure A C --- --- B D --- ---
DSLC-2 terminal
37
39
---
---
38
40
---
---
Phase
L1 / AØ
N
---
---
L1 / AØ
N
---
---
Table 2-8: Voltage measuring - terminal assignment - busbar, 1Ph 2W (phase-neutral)
4 For different voltage systems, different wiring terminals have to be used.Incorrect measurements are possible if both voltage systems use
the same N terminal.